Fires aboard vessels present risks that onshore facilities do not: metal structures conduct heat rapidly, accelerating spread across compartments; external assistance is rarely available; and the confined geometry of engine rooms, machinery spaces, and auxiliary compartments makes manual suppression difficult and dangerous. Condensed aerosol fire suppression addresses these conditions directly — it requires no piping, no pressurized storage, and no dedicated water or gas supply, making it well-suited to the space and weight constraints of modern vessel design. That is why a growing number of vessel owners, fleet operators, and naval architects are specifying Stat-X to protect their most critical spaces.

Fire suppression system selection affects vessel weight, fuel consumption, available space, and crew safety — but these factors rarely enter the conversation early enough. This white paper by Lance D. Harry, P.E., President & CEO of Fireaway, presents the engineering case for condensed aerosol suppression on displacement vessels, with specific weight comparisons, fuel savings data, and a direct analysis of maintenance burden and crew safety implications versus conventional CO₂ systems.













Vessels operating under the International Convention for the Safety of Life at Sea (SOLAS) must carry fire suppression equipment evaluated and approved to applicable IMO standards. For fixed fire-extinguishing systems, this means independent third-party type approval confirming that the system performs as designed across the fire scenarios relevant to shipboard use.
Stat-X condensed aerosol fire-extinguishing systems have received Type Approval Certificate 23277/D1 BV, issued by Bureau Veritas following evaluation in accordance with IMO MSC.1/Circ.1270, valid through 22 October 2030. This positions Stat-X for application in machinery spaces and other enclosed compartments aboard SOLAS-regulated vessels. As with all fixed suppression equipment, vessel-specific installations remain subject to the authorization of the relevant flag state administration and classification society.
The approved product range covers 15 generator models across the E-series and T-series, with machinery space coverage up to 500 m³ — accommodating engine rooms and auxiliary machinery compartments across a broad range of commercial vessel types.
Talk To An Expert
US Coast Guard inspections require US-flagged commercial vessels to carry approved fixed fire suppression systems in designated spaces. Equipment must hold a USCG Certificate of Approval to be accepted during inspections — without it, a vessel cannot demonstrate compliance, regardless of how the system performs in practice.
Stat-X holds USCG Certificate of Approval No. 162.029/257/0. Stat-X was the first condensed aerosol fire-extinguishing system to receive this designation. The COA covers T-units activated by thermal or thermal/manual initiators, for use in enclosed spaces up to 2,568 ft³ (73 m³). The system is approved for Class A, B, and C fires and is accepted for use in both normally occupied and normally unoccupied spaces when designed and installed appropriately — removing a restriction that limits many competing systems.
Stat-X T-units require no piping, no dedicated suppression agent storage room, and no pressurized cylinders. Each unit is self-contained, with a rated service life of 15 years and minimal scheduled maintenance. There are no HFC or PFAS compounds in the formulation — relevant for operators monitoring evolving environmental regulations.
Vessel types covered include workboats, offshore service vessels, barges, tour boats and ferries, law enforcement vessels, yachts, and other recreational craft subject to USCG inspection requirements.
Talk To An Expert

Photo courtesy of: Marine Fire SafetyFire suppression equipment fitted to UK-flagged vessels must be type-examined and approved in accordance with the Merchant Shipping (Marine Equipment) Regulations 2025, administered by the Maritime and Coastguard Agency (MCA). Equipment meeting these requirements may bear the UK Red Ensign Mark — the UK conformity mark for marine safety equipment following the UK’s departure from the EU regulatory framework.
Stat-X holds UK Type-Examination Certificate 81824/A0 UK, issued by Bureau Veritas and authorized by the MCA, valid through 8 April 2031. This certification confirms that Stat-X condensed aerosol systems have been independently evaluated to the relevant standards and may be fitted to UK-flagged vessels through the Red Ensign Mark pathway.
The same compact, self-contained architecture that qualifies Stat-X for other regulatory regimes applies here: no piping runs, no dedicated storage spaces, and no pressurized components. For vessel owners and distributors working within the UK flag state framework, Stat-X provides a straightforward route to compliant fire suppression with minimal installation complexity.
Talk To An Expert
The EU Marine Equipment Directive (MED) 2014/90/EU establishes the requirements for fire suppression equipment fitted to vessels flagged in EU member states. Under the MED, equipment must undergo independent third-party type examination and production quality assurance before it may bear the Wheelmark — the conformity mark that demonstrates compliance with EU marine safety standards and permits placement on EU-flagged vessels.
Stat-X holds EC Type Examination Certificate 81823/A0 MED, issued by Bureau Veritas and valid through 8 April 2031. Certification follows the MED conformity assessment structure: Module B (type examination confirming the system meets applicable standards) combined with Module D (production quality assurance, confirming ongoing production consistency). Fireaway holds ISO 9001 & ISO 14001 certification, supporting the quality system requirements of Module D.
The Wheelmark on Stat-X equipment signals to shipowners, operators, naval architects, and procurement teams that the system has been evaluated under EU law by an authorized notified body — providing the regulatory certainty required for EU-flagged vessel specifications.
Talk To An Expert


Marine Fire Protection Training & Experts Panel: Jim Dickinson Executive Vice President Global Sales, Fireaway Inc. Jason Fuglsby Director of Engineering, Fireaway Inc. Ernie Ellis President, Sea-Fire Marine Ian Bartle...
READ MOREWhy are we still depending on portable fire extinguishers? Workboats are vessels used for commercial purposes, i.e.., they perform some form of “work.” This includes a large portion of the...
READ MOREHow Classification Societies Assess Fixed Aerosol Fire-Extinguishing Systems This article is the third in a three-part series on IMO regulatory frameworks and marine fire suppression approval pathways. It examines how...
READ MOREThis article is the first in a three-part series examining the regulatory frameworks that govern fixed aerosol fire suppression systems in international marine applications. It examines the roles of the...
READ MOREClarifying how international SOLAS compliance and U.S. regulatory approval frameworks relate in practice. This article examines how IMO and U.S. Coast Guard approval frameworks relate in practice — covering the...
READ MOREFor over 200 years, the United States Coast Guard (USCG) has been upholding its mission “to ensure our Nation’s maritime safety, security and stewardship.” A primary component of this mission...
READ MOREFireaway Inc. is proud to announce receipt of the United States Coast Guard (USCG) Certificate of Approval (COA) for our pre-engineered Stat-X® condensed aerosol fire suppression systems to protect Class...
READ MOREEvaluation and Acceptance Pathways for Fixed Aerosol Fire-Extinguishing Systems This article is the second in a three-part series on IMO regulatory frameworks and marine fire suppression approval pathways. It examines...
READ MOREAnswers to common questions from shipowners, naval architects, shipyards, and surveyors evaluating Stat-X® condensed aerosol fire suppression for vessels. For questions about how the technology works, see our general FAQ. For a discussion of the engineering case for aerosol in machinery spaces, see Ask an Expert: Marine Fire Suppression Questions from the Field.
Stat-X fixed systems hold the following marine certificates:
Certificate numbers and issuing bodies are listed on our Approvals and Listings page. The U.S. Coast Guard approval can be verified by searching for Fireaway or approval number 162.029/257/0 in the Coast Guard’s Approved Equipment List (CGMIX). Copies of the Bureau Veritas, MED, UK, and ABS certificates are available from your authorized Stat-X marine distributor or from technical@statx.com. Details of the certification program are in our announcement.
The applicable approval depends on the vessel’s flag, whether SOLAS applies, and the classification society:
Type approval confirms that the Stat-X system design satisfies the applicable evaluation requirements. Every installation remains subject to review and acceptance by the classification society and flag administration for that vessel. For an explanation of how the IMO and U.S. Coast Guard frameworks differ, see IMO and U.S. Coast Guard Approval: What’s the Difference? and From Flag-State Approval to SOLAS Applicability.
Yes. MED certification is accepted by DNV, RINA, and Lloyd’s Register in lieu of separate class type approvals, so parallel type approvals from multiple classification societies are not required. ABS additionally holds its own Product Design Assessment for Stat-X on non-SOLAS vessels. In each case, the classification society reviews the vessel-specific installation, including compartment volume and geometry, ventilation arrangements, obstructions, generator placement, and the detection and control interface. The approval sequence is explained in From Evaluation to Type Approval.
The Bureau Veritas type approval covers machinery spaces up to 500 ³, which is sufficient for the engine rooms and machinery spaces of most workboats, offshore vessels, ferries, and small to mid-size commercial vessels.
Stat-X has been successfully tested in machinery spaces up to 500 m³ in accordance with IMO MSC.1/Circ.1270. While 500 m³ represents the largest tested enclosure, it does not necessarily represent the maximum space Stat-X can protect. Larger spaces may be considered but are subject to engineering evaluation specific approval from the vessel’s flag administration and applicable regulatory authorities.
The U.S. Coast Guard approval covers spaces up to 73 m³ with a maximum height of 16 ft (4.88 m), and the ABS Product Design Assessment covers spaces up to 100 m³ with a maximum height of 4.88 m. Larger spaces are protected by increasing the number of generators, and multiple compartments on the same vessel are protected as separate zones. Projects with spaces outside these envelopes are reviewed by Fireaway engineering with the classification society; contact technical@statx.com.
A Stat-X marine system consists of aerosol generators mounted on the deckhead or bulkheads inside the protected compartment, a means of activation, and, for electrically activated systems, a marine fire detection and release control panel. Electrical (E-series) generators are released by the control panel on confirmed detection, typically from two independent detection zones. Thermal (T-series) generators activate at a fixed temperature (70 °C, 95 °C, or 123 °C) and thermal-manual generators add a manual release, which allows small compartments to be protected without external power.
There are no agent cylinders, no piping or nozzles, and no dedicated agent storage room. The generators are non-pressurized until activated. Mounting hardware and electrical connections must follow the Stat-X Marine Design, Installation, Operation, and Maintenance manual, which is part of the type approval. Product details are on our Electrical Units and Thermal Units pages, and typical arrangements are described on the Machinery Spaces and Engine Enclosures pages.
The engineering comparison with water mist is discussed in Ask an Expert; the figures below quantify the difference.
For a 1,000 m³ engine room on a 4,000 metric ton offshore supply vessel, a conventional CO2 system typically weighs about 4.0 to 4.5 metric tons installed, including cylinders, Schedule 80 piping, valves, racks, and manifolds, and requires a dedicated ventilated CO2 room. An equivalent Stat-X installation weighs less than 0.5 metric tons, including generators and controls, and requires no storage room. The full analysis, including the effect on payload, fuel consumption, and stability, is in our white paper, available on the Marine page.
An independent study presented at INEC 2018 compared systems for the two engine rooms of a 70 m offshore patrol vessel. The high-pressure water mist system weighed 7,500 kg dry and required 108 kW of pump power; the inert gas system weighed 4,800 kg with 26 high-pressure cylinders; and the Stat-X system weighed 480 kg, drew about 1 A of electrical current for initiation, and occupied a small fraction of the space. The paper is available here: Machinery Space Fire Fighting – Modern Alternatives (INEC 2018).
For electrically released systems, the sequence follows the vessel’s approved fire control plan. Confirmed detection triggers the pre-discharge alarm in the protected space, and the control panel starts a time delay during which personnel leave the compartment and ventilation is stopped and closures are secured, as they would be for any total flooding system.
A lock-out or abort switch allows the release to be held. At the end of the delay the generators discharge, filling the compartment with aerosol within seconds. The aerosol remains suspended to provide hold time against re-ignition, and the compartment should remain closed for the hold time specified in the design before ventilation and re-entry are carried out in accordance with the vessel’s procedures.
Thermal generators activate automatically when the fixed-temperature element reaches its set point, and thermal-manual generators can also be released by the crew from outside the compartment.
Under the Bureau Veritas and MED certification, protected machinery spaces are treated as unoccupied during activation. The U.S. Coast Guard approval covers normally occupied and normally unoccupied spaces when the system is designed and installed appropriately. Unlike CO2, Stat-X does not extinguish by displacing oxygen, and the agent is listed under the U.S. EPA SNAP program for use in normally occupied spaces.
The aerosol does reduce visibility and is hot near the generators at discharge, so the compartment is evacuated before release and re-entered only after ventilation, in accordance with the vessel’s procedures. See Is it safe for personnel? on our general FAQ.
Stat-X generators are single-use. After a discharge, the compartment is ventilated and cleaned, the discharged generators are removed, and replacement generators of the same model are installed and reconnected. Because there are no cylinders to refill, no piping to flush, and no hydrostatic testing, restoration is straightforward and can be completed by an authorized Stat-X distributor or a trained service technician at the next port. Any accumulated particulate on equipment surfaces should be cleaned within 24 hours, following the guidance in the Stat-X manual.
Yes, for vessels using HFC-based clean agents. The U.S. Coast Guard’s Marine Safety Information Bulletin 06-22 alerted the maritime industry to the phasedown of HFC-227ea (FM-200) under the American Innovation and Manufacturing (AIM) Act, which is reducing HFC production and consumption in the United States and will require recycled HFCs for servicing fire suppression equipment beginning in 2030.
The Stat-X aerosol contains no HFCs, no fluoroketones, and no PFAS, and it has zero ozone depletion potential and zero global warming potential, so it is not affected by these measures. See the Coast Guard’s MSIB 06-22 and our white paper, What Does the AIM Act Mean for Fire Suppression?
Yes. The U.S. Navy uses Stat-X to protect propulsion gas turbine enclosures on its Landing Craft, Air Cushion (LCAC) fleet, based on full-scale fire testing conducted by the Naval Research Laboratory, and has approved Stat-X for the protection of diesel engine rooms and flammable liquid storage rooms on fleet vessels.
In the United Kingdom, a study for the Ministry of Defence presented at INEC 2018 evaluated Stat-X against water mist and inert gas for minor warship machinery spaces. Naval vessels are generally outside SOLAS, and each navy sets its own equipment standards, so approvals are handled with the relevant naval authority. See our Marine page or contact technical@statx.com for naval references.
The certification scope, including the spaces where Stat-X cannot be used, is discussed in Ask an Expert. For design considerations and typical arrangements in individual spaces, application pages are available for Machinery Spaces, Main Switchboard Rooms, Energy Storage Systems on Electrically Powered Vessels, Paint Lockers and Hazardous Stores, and Wheelhouse and Control Rooms.
Stat-X marine systems are designed and installed by authorized distributors trained by Fireaway, working with the shipyard or owner’s naval architect. To prepare a design and class submittal, the distributor needs:
From this information the distributor produces a design report and drawings for classification society review and surveyor inspection. To find an authorized marine distributor or discuss a project, visit our Marine page or email technical@statx.com.